Thermal & Remote Infrastructure Monitoring

Fixed radiometric cameras on the assets that matter, with temperature thresholds, alarm escalation and a recorded condition history an auditor can read.

Substation steelwork, busbars and disconnectors standing behind a perimeter fence.
Licensed stock · illustrative

01Demonstration

What the camera sees.

Synthesized demonstration. Not a client site and not a survey record.

Thermal / visual comparator

Synthesized · not a client site

VisualInfrared
25°38°50°63°75°
Ironbow palette · apparent temperature
Three-phase cable termination onto a busbar. Drag to compare the drawing against the infrared frame. Readings are published in full below and do not depend on the slider.
Radiometric spot readings for Three-phase cable termination onto a busbar
SpotComponentReading
Sp1R-phase terminationreference46.2 °C
Sp2Y-phase termination45.1 °C
Sp3B-phase terminationanomaly68.6 °C

ΔT vs Sp1

22.4°C

Major discrepancy

Repair immediately. Measured against a similar component under similar loading.

ΔT against band

axis truncated at 32 °C

02Scope

What this covers.

Delivered against

  • NFPA 70B
  • ASTM E1934
  • NETA MTS thermographic survey

Standards worked to. Not a claim of certification — those are listed, with issuing bodies, on the capabilities page as evidence is received.

  • Fixed radiometric thermal camera installation
  • Continuous hotspot detection with temperature thresholds
  • Centralised monitoring and video management
  • Alarm escalation to control room, SMS and email
  • Baseline thermal surveys and inspection reporting
  • Remote site backhaul and power design

03Severity criteria

How an anomaly is classified.

Both reference bases are published here because a threshold quoted without its basis means nothing. Where a comparable component under comparable loading exists, it is the reference — it cancels out ambient and load.

ΔT against a similar component under similar loading
ΔTClassificationAction
1 °C to 3 °CPossible deficiencyWarrants investigation.
4 °C to 15 °CProbable deficiencyRepair as time permits.
> 15 °CMajor discrepancy← measured readingRepair immediately.

Source ANSI/NETA MTS-2023, Table 100.18, Section 9. A reading is only classifiable against the basis it was measured on. Where a comparable component under comparable loading exists, that is the reference — it cancels out ambient and load. Ambient is the fallback, not the default.

ΔT over ambient air temperature
ΔTClassificationAction
1 °C to 10 °CPossible deficiencyWarrants investigation.
11 °C to 20 °CProbable deficiencyRepair as time permits.
21 °C to 40 °CMonitorMonitor until corrective measures can be accomplished.
> 40 °CMajor discrepancyRepair immediately.

Source ANSI/NETA MTS-2023, Table 100.18, Section 9. A reading is only classifiable against the basis it was measured on. Where a comparable component under comparable loading exists, that is the reference — it cancels out ambient and load. Ambient is the fallback, not the default.